Wind 1200 MWSolar 600 MWBattery 400 MW (5h)2040 - On the Path to Net-Zero
Clean 91.4% · Local 85.1% · Net 103 $/MWh (10.3 c/kWh) after export sales (Gross 129)
Cables to New Brunswick: Nuclear 29 MW · Other Imports 700 MW · Exports 610 MW.
Details Nuclear outage 672 h · DR limit 750 MW (Base peak x 1.20) · West Cape 90 MW for export not counted; total wind would be 1,290 MW. See Technical Report.

Electrify PEI

What happens in 2040?

This page is one scenario, not a prediction. It shows what PEI's grid would do, hour by hour, with the wind, solar, and battery in this scenario.

What to look for: The coldest evening - does the peak stay under control? The sunny, windy midday in summer - where does the extra go? And the battery - does it discharge at the peak, and charge when there is surplus?

Charts: All times Atlantic. Pinch to zoom, tap the house to reset.

2040 - On the Path to Net-Zero

Clean 91.4%  -  Local 85.1%  -  Net 103 $/MWh after export sales (Gross 129)

LOAD - AVERAGE & PEAK
Average load 420 MW  -  Peak load 1084 MW
Base peak 622 MW  -  Total 3683 GWh
Base 2986 GWh + Flex EV/WH/HP 696 GWh + Battery charge 216 GWh
Peak hour: Feb 01, 06 PM Atlantic
DR operating limit: 750 MW (Base peak x 1.20) - DR deferred EV 20 MWh, WH 14 MWh. On the coldest day DR is in peak-shaving mode: EV / hot-water / battery charging pause, battery discharges. HP heating and EV must-charge are never deferred.
DEMAND RESPONSE - PEAK SHAVING
Operating limit 750 MW (Base peak x 1.20)
DR deferred EV 20 MWh, WH 14 MWh to later, lower-load hours
Most hours DR is in normal mode: EV, hot water, and battery charge on surplus. On the coldest day DR is in peak-shaving mode: EV / hot-water / battery charging pause, battery discharges. HP heating and EV must-charge are never deferred. Transmission and distribution cannot carry Base + HP + EV + WH + battery charging all at once.
SUPPLY MIX - HOW TOTAL WAS MET
Nuclear Imports: 235 GWh (6.4%)
Local Wind+Solar+Battery: 3132 GWh (85.1%) = Total - Nuclear - Other - Backup
Other Imports: 316 GWh (8.6%) - mix unclear, not counted as clean
Total Imports: 550 GWh (14.9%)  -  Backup: 0.0 GWh
Clean = Local + Nuclear = 3367 GWh (91.4%) = Total - Other - Backup
RENEWABLE GENERATION
Wind: 1200 MW x 42.1% CF = 4430 GWh (120% of load)
Solar: 600 MW x 13.2% CF = 692 GWh (19% of load)
Total RE gen: 5122 GWh (139% of load)
Exports 1925 GWh, Curtailed 233 GWh
BATTERY
400 MW / 2000 MWh (5.0h)
Charged 216 GWh, Discharged 193 GWh, Loss 22 GWh, Cycles 97
EV FLEET - 24 SUB-CLASSES (V34) - PEI-ANCHORED - 6 DISTANCES x 4 VEHICLES
45,000 total = 2,800 already in Base + 42,200 new (only new are in Flex)
Total 147.1 GWh/yr (new only), Peak 165.4 MW, Avg SOC 70%
Modelled average: 3485 kWh/yr per new EV, 227 Wh/km (from the run - total EV energy / new EVs, / 15,330 km/yr, PEI stat 15,300)
Gasoline displaced 59.4 ML/yr ~ 137 kt CO2/yr avoided (same 24-class matrix; car 7.5, SUV 9.5, truck 12.5, van 11.0 L/100km x 2.3 kg CO2/L). Diesel not counted - some trucks are diesel, so this is conservative.
EV methodology - click to expand
24 sub-classes = 6 distances x 4 vehicles, independent - a 40 km/day driver can be in a truck, a 160 km/day driver can be in a car. Distances: 5% @ 160, 10% @ 120, 10% @ 70, 15% @ 40, 30% @ 20, 30% @ 10 km/day = 42.0 km/day = 15,330 km/yr (PEI: 15,300, NRCan). Vehicles, same mix at every distance: 55% SUV (172 Wh/km), 20% car (155), 20% pickup (245), 5% van (210). PEI tilt: Canada fleet SUV 41.9/Car 35.0/Pickup 16.8/Van 6.3; new sales SUV 62.9/Pickup ~20/Car ~12; PEI is more rural/truck-heavy, so trucks 20%. PEI does NOT publish a body-type split - this is the honest gap, flagged to replace when it does. Efficiency hourly from Charlottetown temp that hour, Leaf curve for shape, scaled per vehicle from EPA. Km-weighted fleet 1.19x Leaf. Charger loss x1.10. SOC 30% -> 80% (Dahn, Dalhousie). BEV/PHEV: PEI 2025 ZEVs are 40.5% PHEV (810/1,999); PHEVs drive 60% of km on electricity. Visitor uplift: 1.71M visitors, ~1M bridge vehicles/yr, +4% May, +8% Jun, +12% Jul/Aug, +8% Sep, +4% Oct - shown as ev_visitor_MW. Timer 11:30pm-6:30am Atlantic, Smart any hour. No brands, no DC fast charging, no V2G.
HEAT PUMPS
65,000 homes total = 20,000 already in Base + 45,000 new (only new are in Flex)
Electricity 283.1 GWh/yr (new only), Thermal 787.5 GWh/yr, Avg COP 2.78
Heat delivered displaces fossil heat (oil / propane / biomass) - not split here, because PEI's remaining fossil heat mix is small and mixed, and this model does not track which fossil fuel each home used before.
HOT WATER
40,000 tanks total = 25,000 already in Base + 15,000 new (only new are in Flex)
Domestic 3000 kWh/yr/home, Commercial 8000 kWh/yr/unit
Tank 6.3 kWh, Element 4.5 kW, SOC 0.40-0.85 = 2.8 kWh flex (0.45 x 6.3 kWh tank)
ECONOMICS (2024 CAD)
CAPEX: Wind 1200 MW x $2.25M/MW = $2700M, Solar 600 MW x $1.80M/MW = $1080M, Battery 400 MW / 2000 MWh = $860M
Total CAPEX $4640M
Annualized (CRF 6% - 30yr wind/solar, 20yr battery): Wind $258.2M/yr = LCOE $58/MWh (5.8 c/kWh) - Solar $89.5M/yr = LCOE $129/MWh (12.9 c/kWh) - Battery $75.0M/yr = $388/MWh delivered
Nuclear Imports $26.5M/yr at $113/MWh - Other Imports $25.3M/yr at $80/MWh
Gross cost $474.5M/yr / 3683 GWh = Avg 129 $/MWh (12.9 c/kWh)
Exports sold 1925 GWh x $50/MWh = $96.3M revenue
Net cost to islanders $378.2M/yr = $474.5M gross - $96.3M export sales
Net $103 $/MWh (10.3 c/kWh) after export sales - this is what islanders effectively pay
WEATHER - Charlottetown 2025 (MERRA-2 / actual)
Mean 7.4deg C, Min -15.7deg C, Max 30.5deg C, HDD18 4062, CDD21 53
Precip 846 mm total, Snow 2426 h >2 kg/m2, Max snow 44.6 kg/m2, Hours <-10deg C 259, Hours <-15deg C 6
Snow derate: solar to 20% when snow >2 kg/m2

Powered by PEI-Dispatch - Hourly electricity dispatch model for PEI. Back to Electrify PEI home